Isolation Room Pressure Controller:
FMS-1630L

TRIATEK's FMS-1630 Series Isolation Room Controller for building systems using the BACnet open protocol, room pressure can be monitored and controlled with Triatek’s FMS-1630B (BACnet version single room isolation monitor / controller). This unit is a precision measuring system for ultra low pressure or flow.

FMS1630 Room ControllerHospital patient rooms can be held to safe negative pressure for contagious isolation meeting the Center for Disease Control and Prevention Guidelines for Tuberculosis Isolation, or pressurized for protective isolation.The FMS-1630 is ideal for other isolation applications such as laboratory and clean rooms.

Quick Specs
Optional Ext.l Remote Sensor Max. Distance: 4,000 feet
Power Supply: 24 VAC/DC +/- 10%, 10 VA
Pressure/Flow Inputs: Up to 0.2" W.C.
Door Switch Input: Dry Contact
Relay Rating
(2 ea):
2.0A @ 24VDC/VAC, .2A @ 120 VAC
Analog Outputs: Linear Proportional to Pressure or PID
  Floating Control
LCD Display: 4 Line x 16 Character
LCD Characher Height: 0.19 Inches
Communication: BACnet