Triatek Products
Actuators
  -
(ACT-FA-8001)

Fume Hood Controllers
  - HMS 1650 Bacnet/N2
  - HMS 1650 LON
  - HMS 1600 LX
  - HMS 1600L (LON)
  - HMS 1600
  - VAV 1000

Lighting Products
  - LP3500 Lighting Panel
  - LP-CT Lighting Panel

LITE Monitors
  - FMS 1650LITE
  - HMS 1650LITE

Network Gateways
  - Trigate Large
  - Trigate Small

Remote Monitors
  - CMS 1650
  - FMS 1650R

Room Pressure Controllers
  - FMS 1650 (Bacnet)
 
 - FMS 1650L (LON)
  - FMS 1650T (Thin)
  - FMS 1630L
  - FMS 1630B
  - FMS 1630
  - VAV 1000

Sensors
  - Motion
  - Sash Height

Venturi Valves
  - Overview
  - Operation
  - Options
  - Performance
Room Pressure Controller:
FMS-1650 (BACnet)

Building on over 18 years of proven isolation room control experience, Triatek offers its latest generation of FMS series Isolation Room Controllers – The FMS-1650.

room pressure controllerWith an integrated precision measuring system and an aesthetically pleasing, user friendly, touch sensitive, full color TFT display, configuring room parameters has never been easier. Highly sensitive, pressures or flow to 0.0001”WC can be measured with the FMS1650.

Building automation systems using one of the popular open protocols (BACnet, Metasys N2) easily integrates the FMS-1650 into the current architecture without additional programming. The 6 analog and 4 digital inputs, plus 4 PID and 4 relay outputs, also allow for a variety of configuration options and increased flexibility.

Other features include:

• Simultaneous display of pressure, temperature, humidity & air changes Password protection
• Audible alarm delay
• Optional custom logo available
• Optional secondary, non-interactive flush or surface mounted

 

Quick Specs
Pressure Range: ±0.2500”WC
Optional Ext.l Remote Sensor Max. Distance: 4,000 feet
Accuracy of Measurements: ±0.00125
Analog Inputs: (6) 4-20mAdc,
0-5Vdc or 0-10Vdc
Analog Outputs:

(4) 4-20mAdc (BACnet)

0-5Vdc or 0-10Vdc

Thermistor Inputs: (2) NTC Type 2 or 3, 10kΩ @25˚C (BACnet or LON w/optional resistor)
Digital Inputs: (4) Active-High or Active-Low
Relay Outputs: (4) 1A@24Vdc
LCD Size: 3.2” diagonal
LCD Type: Transmissive
Communications: BACnet, Metasys N2