Fume Hood Pressure Controller & Monitor:
HMS-1650 (BACnet and N2 Native)

Built on the same fundamental philosophy as its predecessor, the HMS-1650 is the next generation of fume hood monitors. Featuring a user friendly, touch sensitive LCD screen, configuration has never been easier. And with its “at a glance” color coded screen, users will immediately know if the fume hood is safe for use.

HMS1650 BACnet fume hood controllerThe Triatek HMS-1650 uses a dedicated face velocity flow sensor input, as well as a second input, for truer readings with a high degree of reliability. Additionally, this precision instrument can not only control flow conditions, but also monitor them using ultra-sensitive thermal anemometry. Connections to remote monitoring or automated systems is also possible for monitoring functions only. Highly customizable, the HMS-1650 series can be set up to display most any hood parameter or process and has available inputs for sash position sensors.

Other features include:
• Multiple alarms for face velocity & sash
• Programmable display
• Override switch input
• Non-volatile memory
• Password protected

Quick Specs
Face Velocity Range: 0 - 200 FPM
Accuracy: ±2 FPM
Analog Inputs: (4) 4-20mAdc, 0-5Vdc or 0-10Vdc
Analog Outputs: (4) 4-20mAdc, 0-5Vdc or 0-10Vdc
Thermistor Inputs: (2) NTC Type 2 or 3, 10kΩ @25˚C
Digital Inputs: (4) Active-High or Active-Low
Relay Outputs: (4) 1A@24Vdc
Metasys N2 Network: Two-wire twisted pair,
 RS-485 signaling
Control Signal Wire Size: 18 AWG minimum
Recommended Cable: Belden 3107A
LCD Size: 3.2” diagonal