TRIATEK's PM-1000 Series Watt-Hour Meter measures power in Watts-Hours and provides a pulse output proportional to energy consumption.
Utilizing three current transformers and up to 480 volt service on single and polyphase power systems, the unit performs necessary factoring and math functions to calculate energy use in Watt-Hours. Watt-Hours are transmitted as a dry contact closure rated at 120V, 0.3A, -10VA maximum for remote control or monitoring applications. The standard Watt-Hour calculation factor is calibrated to output 5 watt-hours per count. However, to increase the pulses the unit can be ordered with other Watt Hour per count factors. The equation for determining KWH is the potential transformer ratio multiplied by the current transformer ratio multiplied by the Watt-Hour/Count ratio divided by 1000. For example, if there is no potential transformer and if the current transformer ratio is 600:5, and the Watt-Hour/Count is 5, then the KWH value per closure on the PM-1001 would be 0.6 KWH (600÷5)*5)/1000.
The PM-1000 Series Watt-Hour Meter is housed in a general purpose enclosure for mounting in a panel or on a flat surface.

Selecting Part Numbers:
1. 5000 Series Options:
 
2. 5001 Series WH/Count Options:
 
3. 5101 Series WH/Count Options:
 
Insert the desired numbers and/or letters of each drop down box above into the corresponding boxes below to determine the part number.

    1. 2. 3.
 Part Number:
PM-1 -

 Features & Benefits

 Applications

  • Measures Hours in Watt-Hours
  • 120/208 OR 277/480 Voltages
  • STANDARD 0-5 AMP AC INPUTS
  • Dry Contact Pulse Output
  • .625, 1.25, 2.5, OR 5 WH/C Ratios
  • Easy Installation
  • One Year Warrantee
  • Energy Management
  • Industrial Automation
  • Chiller Energy Monitoring
  • Sub Metering
  • Demand Monitoring
  • Energy Use Monitoring

Specifications

Electrical

Voltage .................................................................... 120/208 and 277/480
Phase ................................................ 3 Phase- 3 Wire or 3 Phase - 4 Wire
Current Input ..................................................... 0-5 Amp, 3 CTs required
Burden ............................................................................................... 2VA
Power Factor ................................................................ .5 Lead to .5 LAG
Power Supply .................................... 208/240/480V, 50/60HZ, 2.5 Watts
Accuracy .................................................................. + 0.5% Rated Output
Closure Rate .................................................................. ~250 Milliseconds

Mechanical

Dimensions ........................................................... 7.75"W x 4.0"H x 2.0"D
Shipping Weight ......................................................... Approximately 5 lbs.
Mounting ........................................................... Wall mount or Flat Surface

Environmental

Operating Temperature .......................................................... 32° to 125°F
Operating Humidity ................................. 10% - 95% RH, Non-condensing

 

 