Triatek Trigate (Large)
The Trigate Series includes two protocol translator gateways to enable devices using one protocol to communicate with devices using another protocol. An example is a fire alarm panel using a proprietary manufacturer’s protocol needing to supply alarm information to a building automation system.
Regardless of the model employed, the versatile Trigate Series offers connectivity options for the most popular protocols including LONWORKS®, BACnet, Modbus, JCI-N2, etc. Whereas the larger unit is primarily used for networks with up to 4095 network variables, the smaller and more economical unit is used for those networks that have less than 1000 network variables.
Both models come with all of the necessary software and instructions for configuration.
| LonWorks: | FTT-10 Twisted Pair; 4095 Network Variable Capability; UNVT or SNVT Variable Support; Explicit (Polled Mode) or Implicit (Bound Mode) Addressing |
| Ethernet Ports: | (2) 10baseT RJ45 Connector |
| Serial Ports: | (8) RS-232 Ports, RJ45 Connector |
| ISA Card Slot Adapters: | (2) RS-485 Ports, Terminal Connector |
| Transmission Rate: | Up to 115K Baud |
| Host PC Connections: | Ethernet 10baseT; RS-232 or RS-485 |
| LED Indicators: | Power, Run, System Error, Configuration Error |
| Power Requirements: | 120/220 VAC, 50/60 Hz 1 amp |
| Operating Temperature: | 32 - 144°F (0 - 60°C ) |
| Dimensions: | 7.5”W x 12.0”D x 2.2”H (19.1 x 30.5 x 5.6 cm) |