Yes.
The FMS-1650 and FMS-1655 have 4 analog inputs available. Follow the directions below to configure each analog input.
Tap the display in a space where no icons or text are present to activate the Main Menu Setup. Navigate the menus as follows:
Main Menu Setup >> Select System Setup >> Select Analog Inputs >> Select Analog Input # (Note: Analog Input 1 defaults as Primary Pressure Input) >> Select Input Type as Pressure >> Select Sensor Type as Rmt Digital 4-20mA >> Select Disabled Linearization and Select Normal Input Mode >> Select Next >> Select Engineering Units and Select Range >> Select Next >> Select Sensor Range of +/-0.25 >> Select Next >> Enter ISO Setpoint >> Select Next >> Enter Dead Band >> Select Next >> Repeat for Analog Inputs as Needed